I'm looking at a design that calls for bare copper ground conducotrs to be used for grounding the various PV modules/structures in an array. I was wondering however if there was anything in the NEC that required these conductors to be bare, or if they could be THHN conducotrs with a jacket? I do not believe there is anything preventing the use of THHN cables other than it will be easier to terminate the bare copper condutors to the modules since you dont have to strip the cable to land it on grounding lugs.
For all the ground cables from the combiner boxes to the inverter, etc.. regular THHN cable is called for the ground? Is there anything in the NEC that dictates what type of cable bare conductor or otherwise is to be used for PV installations?
I'm looking at a design that calls for bare copper ground conducotrs to be used for grounding the various PV modules/structures in an array. I was wondering however if there was anything in the NEC that required these conductors to be bare, or if they could be THHN conducotrs with a jacket? I do not believe there is anything preventing the use of THHN cables other than it will be easier to terminate the bare copper condutors to the modules since you dont have to strip the cable to land it on grounding lugs.
For all the ground cables from the combiner boxes to the inverter, etc.. regular THHN cable is called for the ground? Is there anything in the NEC that dictates what type of cable bare conductor or otherwise is to be used for PV installations?
The NEC allows insulated or bare EGCs.
However if the design calls for bare why would you use anything else?
I am the one behind the design and have the contractor asking if he can use either.I don't think you can use THHN where the wiring is outdoors and exposed, but either way I'll wager that the installer would prefer to use solid bare copper. Having to strip insulation at every lug would be a pain.
I specified bare because I thought it would be easier to terminte on module lugs.
I want to give contractor the option of using either, but want to make sure there are no code issues with using either.
So are you esentially saying that ground conductors weather they are ECG, GEC's, etc.. can be either bare or stranded (THHN)? If they want to use stranded for grounding the modules I do not see an issue with this, I just want to make sure this is not violating any code issues?
I don't think you can use THHN where the wiring is outdoors and exposed, but either way I'll wager that the installer would prefer to use solid bare copper. Having to strip insulation at every lug would be a pain.
So are you saying that you cant use stranded cable where not protected in a raceway such as conduit?No, I am saying that I don't think THHN can be run outside of conduit outdoors whether it is stranded or solid. You could run USE-2 as an insulated EGC, I guess, but it would be very expensive and a real pain to work with. Bare copper is the industry standard for this application for a reason; it's easy to work with and cheaper than insulated wire of the same gauge. I don't see why they would want to use anything else. Has your contractor ever done solar before?
No, I am saying that I don't think THHN can be run outside of conduit outdoors whether it is stranded or solid. You could run USE-2 as an insulated EGC, I guess, but it would be very expensive and a real pain to work with. Bare copper is the industry standard for this application for a reason; it's easy to work with and cheaper than insulated wire of the same gauge. I don't see why they would want to use anything else. Has your contractor ever done solar before?
You can get bare stranded copper, you know, but I've never seen it used as a solar module EGC; you'd have to confirm that the lugs are listed for it. Also, your AHJ may have something to say about this.
Just so I am correct on the terminology.
Bare copper conductors (lets say #6) are typically a solid conductor correct? But it sounds like you are also saying you can buy a bare copper stranded conductor for the same purpose as long as equipment is UL listed? Typically though bare copper is solid.
Insulated cable is stranded. Even though it is stranded it can still be used as an ECG and does not violate the NEC, it would just be more difficult to use.
So in summary:
1) For an EGC Bare solid or stranded can be used
2) For an EGC Insullated stranded can be used (has to be rated for outdoor exposure)
3) Either bare/stranded, insulated/non-insulated can be run inside conduit?
Is this correct
I wouldn't use stranded wire THHN wire for an exposed EGC on a PV array, because I wouldn't trust it to be as mechanically durable if the insulation decays in the sun and comes off. That said, I don't know where in the NEC it is clearly prohibited to use stranded wire.
If it is okay to use a bare solid conductor for an EGC, then it stands to reason that it is okay to use an insulated solid conductor (THHN or otherwise), because the insulation is superfluous to the purpose and it does not matter if it decays. Perhaps the contractor can find insulated wire at a cheaper price because there is more supply, and is willing to strip insulation because he thinks he will still save money. I would say that is his prerogative, as long as it solid wire.
I have both heard and know from experience that it is often a stupid idea to run larger solid conductors inside conduit, bare or otherwise. I would tell you not to run a bare #8 ground inside 3/4" conduit because your wire pull will turn a good day into a bad one. But it doesn't violate the NEC AFAIK.
Written by Don Schultz, trueCABLE Senior Technical Advisor, Fluke Networks Copper/Fiber CCTT, BICSI INST1, INSTC, INSTF Certified
So, here you are with your brand-new shiny tools and Ethernet cable and want to start installing it. You made sure to purchase thousands of feet of ultra-high-quality stranded copper cable and have every intention of running it to 800 feet. What could go wrong? If you hear the train getting into a wreck outside your window, that is exactly what you will hear when you go through the pains of installing the wrong cable type and expecting it to work properly.
Stranded copper Ethernet cable is used primarily for short patching applications. Patching applications means from a wall mounted keystone jack to your end device (like a TV or computer) or from a patch panel to an Ethernet switch. Stranded copper Ethernet is typically already terminated at both ends with 8P8C (aka RJ45) plugs and sold in pre-cut and pre-packaged lengths.
If your intention is to permanently install your cable inside your structure, take back the bulk stranded copper stuff. You need solid copper conductors for structured cable.
What is the difference between solid vs. stranded ethernet cable? Doesn’t copper = copper? Yes and no. Yes, copper is good. CCA or Copper Clad Aluminum is bad, which this article explains: Check Your Specs, CCA is Different from Solid Copper.
Another significant difference between solid and stranded copper is how they are terminated in the field. Solid copper is best terminated with IDC style terminations such as keystone jacks, patch panels, and field termination plugs. 8P8C (aka RJ45) connectors are typically only used on factory pre-made stranded copper patch cords, but there are some exceptions. See Choosing the Right Termination - Keystone Jack vs RJ45 Connector vs Field Termination Plug.
If you want to learn more, please visit our website zhuhaicable.
Using the correct type of copper conductor is key when installing Ethernet cable. It does not matter what Category type of cable for purposes of this discussion. Copper comes in solid or stranded, and both have pros and cons and specific uses.
How does each solid vs. stranded ethernet cable conductor type look inside an Ethernet cable?
Stranded copper Ethernet cables have their place too. In a pinch they are great for connecting two pieces of equipment together temporarily. Stranded copper Ethernet cables, when sold as patch cables, will have RJ45 connector plugs on both ends.
Here is an installation graphic that will help distill solid vs. stranded ethernet cables:
So, there you have it. Selecting the correct type of Ethernet cable has more to do with Category and jacket type. There is more to the decision, and when installing your Ethernet cable you want to weigh the pros and cons and use the right type! With that, I will say…
HAPPY NETWORKING!
trueCABLE presents the information on our website, including the “Cable Academy” blog and live chat support, as a service to our customers and other visitors to our website subject to our website terms and conditions. While the information on this website is about data networking and electrical issues, it is not professional advice and any reliance on such material is at your own risk.
If you want to learn more, please visit our website Bare Stranded Copper Conductor.